Typically, 5A secondary although 1A secondary is available. Can be single or multi ratio (MR). Rule of thumb, select a ratio slightly larger than the rating of the circuit to be protected. Class C is the most. Distance relays measure impedance (Z = V/I) to detect faults. Protection selectivity is partly. Primary side is the line current and secondary side is connected to the relay., 600:5 means that. 019,024,025,026,027 overview) Sample application, Global settings Phase Fault Protection 87 – Phase Differential Current 50 – Instantaneous Phase Overcurrent 50DT – Definite Time Overcurrent Ground Fault Protection (High- Impedance Grounded Gens) 59N – Neutral Overvoltage with accelerated schemes. PSM represents how many times the actual current is above the relay's current pickup setting. Setting calculation: We will drive settings for Station-A end relay of a 220kV line to station-B.